Abstract
This paper analyses the unusual mal-operation of the differential protection for transformer current differential protection during the external fault. The mal-operation reason is researched in detail, based on the mathematical analysis, the simulation, and the field recorded fault data analysis. It is disclosed that the CT saturation leads to the maloperation. Based on this, this paper analyses the improvement for the CT saturation identification method, and discusses the CT selection principles. This paper is aimed at attracting the attention on the problem of the CT saturation and proposing the reference of the analysis method the countermeasure for this problem.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.