Abstract

This study performs the numerical simulation of hydrogen dispersion in a partially open space. The space under investigation measures 2.9 m × 1.22 m × 0.74 m and a leak flow rate of 2 standard cubic feet per minute is assumed. The effects of various roof vent positions and their areas on the ability to recognize the dispersion and accumulation of hydrogen, and its natural ventilation, are shown and discussed. Based on the results, this paper proposes an innovative approach to the sensing-based adaptive risk mitigation control of hydrogen dispersion and accumulation in a partially open space. By adaptively opening roof vents near the leak source, and closing other neighboring roof vents, concentrated hydrogen is exhausted rapidly and efficiently. It is also shown that cases exist where sufficient area of the proposed adaptive roof vent can be determined by the finite-time sensing of hydrogen concentration near the roof. The effects of the delay time of a sensor, and a method to cancel these effects, are also discussed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.