Abstract

In order to improve the operation efficiency of the gas engine heat pump system (GEHPs) and avoid the engine deviate from its economic zone, an energy storage system was introduced to the GEHPs. The gas engine heat pump system with energy storage system (ESGEHPs) is divide into three modes, and the control strategy is presented. The relationship of the speed of the engine, the fuel-consumed rate, gas engine thermal efficiency of the ESGEHPs and real-time building load was studied in the typical day, and comparison was taken with the GEHPs. The experimental results show that the ESGEHPs is more matching the real-time building load with a higher operation efficiency. The primary energy ratio (PER) of the ESGEHPs in three modes was increased by 67.87%, 9.5% and 32.66% compared with the GEHPs, respectively. The ESGEHPs could provide a more stable operation characteristic and higher PER than the GEHPs with a little energy loss.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.