Abstract

Current transformer (CT) is wildly used in electrical measurement and relay protection. In order to improve the power system stability in DC bias, the CT performance of anti-DC is necessarily to be enhanced. Based on the Jiles-Atherton theory, the magnetization characteristics of iron core with different air gap was analyzed in this paper. A simulation model was established using the Simulink toolbox, and the ratio error and angle error were investigated in different air gap length. Simulation result shows that the maximum magnetic density of iron core almost stays uncharged with the addition of air gap. Furthermore the slope of magnetization curve decreased, which leads to the increase of iron core saturation current. Current transformer with closed and air gap iron core possesses a stable measurement error in condition of severe DC bias.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.