Abstract

In order to analyze the way of improving the cooling effect of the data center with the UFAD system, the HVAC simulation software—Airpak—was applied. Numerical simulations for the interior temperature of the rack at different porosity ratios were carried out, and the simulated results indicate that the way of partly enhancing the porosity ratio of the front door and back door can improve the cooling effect. To solve the issue of the thermal current recycle in the exhaust outlet and airflow distribution disorder, the measure of the cold aisle regional closure was taken, and the comparison of data before and after the closure of the cold aisle proved its positive influence on the cooling effect: to lowering the inlet air temperature of racks, to improve airflow distribution inside and outside of the rack and to solve the thermal current recycle in the exhaust outlet.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.