Abstract
Qualitative theoretical analysis about air pressure influence upon the gas concentration of a fire plume was given, different scale n-heptane pool fires were conducted in a small and a standard compartment room in Lhasa and Hefei, respectively. The experimental results show that, in Lhasa, the average mass burning rates in the small room and the standard room both decrease, burning time increases at about 53% in small room and 45% in standard room more than in Hefei. Whereas for maximum changes of CO concentration, in the small room, in Lhasa, CO concentrations reach about twice bigger peak values at larger increase rates than in Hefei. While in the standard room, in Lhasa and Hefei, there are no significant changes for CO concentration, which agrees well with the theoretical analysis results.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.