Abstract

AbstractIn order to determine the safe evacuation time under definite condition of supermarket fire, in this paper, using numerical simulation method, the study for quantitative analysis of supermarket performance-based fire protection design, based on the heat release rate curve fended by experimentation, obtained the formula of heat release rate and time : $$ Q = \left\{ \begin{array} {ll} 0.082{t^2}kw (0 \leq t \leq 180s)\\ 2755kw (t\succ 180s).\\ \end{array} \right. $$ Based on the formula of heat release rate and time to determine the safe evacuation time is new and original in this paper, this can be used in fire protection design and fire protection performance evaluation.Keywordssupermarketperformance-basedfire protection analysis

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.