Abstract

The paper presents experiences gathered during many years of utilizing the current-meter and pressure-time methods for flow rate measurements in many hydropower plants. The integration techniques used in these both methods are different from the recommendations contained in the relevant international standards, mainly from the graphical and arithmetical ones. The results of the comparative analysis of both methods applied at the same time during the hydraulic performance tests of two Kaplan turbines in one of the Polish hydropower plant are presented in the final part of the paper. In the case of the pressure-time method application, the concrete penstocks of the tested turbines required installing a special measuring instrumentation inside the penstock. The comparison has shown a satisfactory agreement between the results of discharge measurements executed using the both considered methods. Maximum differences between the discharge values have not exceeded 1.0 % and the average differences have not been greater than 0.5 %.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.