Abstract

Abstract —The occurrence of fault in electrical power system operation is inevitable. The causes of fault in electrical power transmission and distribution system for instances are lighting strikes on transmission canal, tree collapses, or short circuit inter-phases to the ground. In order to protect the equipment and the whole electrical system in Sengkaling Substation and to reduce the short circuit fault current quickly within timeframe of ½ cycle, it requires Superconducting Fault Current Limiter (SFCL) which is going to be placed on the bus that comes close to a critical point. The designing and analysis on the system of before and after hybrid SCFL installment utilize PSCAD software. The simulation result obtained by installing hybrid SFCL in incoming bus 2 (20 kV) was that hybrid SFCL was able to reduce short circuit fault current in ½ initial cycle with L-G fault of 16.77 kA changed to 5.9 kA, L-L-G fault of 35.38 kA changed to 9.15 kA, L-L-L-G fault of 38.36 kA changed to 9.8 kA, and L-L fault of 28.89 kA changed to 4.35 kA. The average percentage of short circuit fault current that was reduced by hybrid SFCL was 74.12%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.