In this paper, a complicated DC line fault taken place in ±800kV Chu-Sui HVDC transmission system is introduced. During this fault, DC line protection, DC filter differential protection and 82HSNBS protection of another pole acted, and two poles were stopped successively. Based on the theory of HVDC protection and control system and the transient recorders, the processing of the accident is analyzed, and combined with the interrelationship of bipolar DC line as the lightning strike, the characteristics of current transducers of DC filter and the influence of bypass switch closing, the improving suggestions are discussed, and some improving suggestions had put in practice.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.