Abstract

The evaluation of explosion-proof electrical equipment for certification is particularly important given the risk of explosion and must be minimized. This in order to ensure the safety of life, health of workers, to prevent damage to goods and the environment when they meet the essential security requirements at European level. Directive 2014/34 / EU states that equipment used in explosive atmospheres must be designed to operate without endangering the environment for which it is intended. This paper proposes the study and evaluation of the requirements for flameproof enclosures. In order to verify explosion protection, the representative samples made available by explosion-protected equipment manufacturers are tested under the worst possible conditions that may occur in practice.

Highlights

  • This paper deals with the analysis of explosion protection characteristics for the flameproof enclosures cable entries

  • Several studies were made on the reliability of electrical equipment and installations

  • Types of protection represents all the specific measures that are applied to electrical equipment in order to avoid the ignition of the explosive atmosphere surrounding the equipment

Read more

Summary

Introduction

This paper deals with the analysis of explosion protection characteristics for the flameproof enclosures cable entries. According to IEC 60079-1/2014, the flameproof characteristics of the enclosure are not altered if all entries meet the specific requirements given in this clause and shall be one of the following:. The requirement for at least eight full threads is to ensure that at least five full threads will be engaged when the part is installed in a threaded entry, taking into account the presence of any chamfer or undercut. This requirement is not intended to apply to integral cable glands or similar entry devices provided, as an enclosure part, by the manufacturer

Threaded holes
Non-threaded holes
Cable glands
Conduit sealing devices
Plugs and sockets and cable couplers
Bushings
Blanking elements
Verification and tests
Cable glands and conduit sealing devices with sealing ring
Conclusion
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.