Abstract
Different synthetic methods are scrutinized as to the applicability to vacuum breakers. Skeats method with resistor is brought forward and discussed from the viewpoint of breaker failure modes, interruption and circuit phenomena. Criteria for choice of resistor are given. Comparison tests using this method and direct method were performed. The results support theoretical conclusions by experimental verification of equivalency for the tested vacuum breaker. The method offers practical and economical advantages over current injection and is also suitable for multiloop and duty cycle testing.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.