Abstract

Heat transfer rate was experimentally determined in the post-CHF region of a steady-state two-phase flow of a refrigerant in a vertical tube with swirl induced by twisted-tape inserts. Experiments were performed with the vertical flow of refrigerant-113 in a tube with inside diameter of 7.75 mm, a heated length of 3.66 m and mass flux of 375–535 kg/m2s for swirl flow at a pressure of 0.184 MPa. Four tapes were used with twist-ratio of 2.5 to 9.2 for swirl flow. Liquid heating produced the low wall-superheat in the post-CHF region at steady-state, which is typical of heat exchanger operation. Superheated vapor measured at the test section exit in most tests ensured that entire post-CHF region was included. All refrigerant-113 data were compared with the data of water and refrigerant-12. The existing post-CHF heat transfer correlation of swirl flow was modified to predict the magnitude and trends of the data of the three fluids such as water, R-12 and R-113.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.