Abstract

In view of the current direct supply situation of our coal mines high voltage distribution networks commonly used 6kV or 10kV electric cables,on the base of describing mechanism of three different neutral point grounded of underground high voltage distribution networks,detailed analysising three different grounded way of high-voltage power grid parameter sensitivity of leakage protection. The results show that, mine the sensitivity of the high-voltage grid leakage protection and start zero-sequence voltage have a great relationship, the greater the zero-sequence voltage setting value, the device's ability to detect leakage faults weaker corresponding lower sensitivity.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.