Abstract

The partial discharge on the insulator surfaces usually occurred in the distribution system. The influence of water droplets is investigated in this paper. This experiment used a circular resin specimen under High Voltage Alternating Current (HVAC) field stress that was applied to the electrodes with a diameter of 2 mm and with a distance between both electrodes of 35 mm. For this methodology, both a single droplet and also double droplets were used on surfaces and the voltage level was adjusted by 15 kV. Results showed that, firstly, the corona phenomenon occurred around the circular electrode after the water droplets on the specimen surface were stretched to each other, but the double drops took a lower voltage level for the stretching than the single drop. In addition, the double drops acted as a bridge, allowing an electrical field to be generated from both electrodes. This pulled them, easily resulting in arcing. In conclusion, water droplets are a main factor to the aging that occurred on the insulators surfaces and this effect is presented in this experiment.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.