Abstract

AbstractIn order to meet the operating requirements during both winter and summer, a thermosyphon heat exchanger unit used to recover energy from the exhaust air needs to be adjusted for its inclination angle by a regulation mechanism. In this paper, the factors that affect the heat transfer efficiency of the thermosyphon heat exchanger was analyzed and the unit practical operating data in a shopping center was studied. The unit optimal operating mode was acquired due to the influence of the unit inclination angle on the temperature effectiveness under a wide temperature change of the outdoor air. In addition, the inclination angle regulation mechanism uses a programmable logic controller (PLC) to control the unit to work at the optimal operating mode. The unit charged with R410A working fluid worked well and was highly effective.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.