Abstract

In this paper, starting from the active network loss formulas and wind characteristics, it is pointed out the reactive power loss and reactive flow is the major impact of wind power integration on power system loss. The reactive power loss formulas of box-type transformer, main step-up transformer, wind farm collector line and connecting grid line are analyzed. Next the reactive power loss of transformer and transmission line is described in detail. Then put forward the loss reduction measures that installing SVC on the low voltage side of the main step-up transformer and making the doubly-fed wind generators send out some reactive power at an allowed power factor. Use the case of Gansu Qiaodong wind farm to verify the effectiveness of the proposed measures.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.