Abstract

During a recent northern California earthquake of magnitude 4.4, a newly-built hilltop home experienced no structural damage, but some unexpected nonstructural damage. The golden sandstone veneer covering the top portion of an exterior wall dislodged and fell to the ground. The owner hired a consulting engineer to investigate why the damage occurred and how to repair the wall. Given the extent of the stone veneer throughout the house – cladding both exterior and interior walls; in the bedrooms, living room, and kitchen – it became important for the engineer to also determine the extent of the problem throughout the house. The cause of the failure was the contractor’s omission of steel wires and dovetail anchors, and the poor bond between the stone and mortar. Repair recommendations consisted of providing supplemental out-of-plane anchorage for the stone veneer.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.