Abstract

Multizone network airflow analysis is used to analyze stack and mechanical system effects on the distribution of three representative biological agents in a prototype 40 story building. This approach relies on mass balances to compute airflow and contaminant transfer between the building zones. The analysis considers stack effects caused by cold outdoor temperatures, unintended positive and negative pressurization of the floor on which the release of the agent occurs, and three levels of contaminant removal using a combination filter/UVGI system. The results show that vertical shafts, such as stairwells and elevator shafts provide significant routes for contaminant transfer between floors, even when these floors are served by different air handling systems. Because the air moving through these pathways does not pass through an air handling system, this type of transport is not as easily reduced by filtering. However, commercially available filters were able to reduce contaminant concentrations substantially in zones that receive contaminants primarily due to recirculation through the air handling system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.