Voltage unbalance is a common phenomenon in AC power network. This disturbance can cause on the three-phase induction motors connected to the power supply system serious ill effects such as overheating, drop of efficiency and reduction in output torque. Therefore, operation of an induction motor for any length of time above 5% of voltage-unbalance condition is not recommended and on-line voltage unbalance monitoring is required from economical reasons. In this paper a new method of evaluating the degree of unbalanced voltage in power network is proposed. This new approach uses voltage space phasor geometrical locus in polar coordinates based on a modified “a-b-c” to “d-q” coordinate transformation which gives the possibility to localize the unbalanced phases and to appreciate the severity of the voltage unbalance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.