Abstract

A Parallel Path Wet/Dry configuration and a high-precision airflow regulation method are implemented in order to retrofit an existing wet cooling tower. The modifications are intended to reduce water requirements and fan power consumption of a 12-cell wet tower. The proposed method of airflow control takes advantage of fans with variable frequency drive to regulate airflow with high accuracy. A number of simulations are carried out to predict different operating factors of the wet and hybrid towers. Experimentally obtained values of water consumption demonstrate the validity of those obtained using the computer simulations. According to the results, the accurate airflow control prevents sudden fluctuations in requisite fan power and water consumption rate and causes up to 64.6% decrease in fan power consumption. The results reveal that using the proposed wet/dry approach results in an average 9.4% decrease in water consumption. Given the relatively low degree of modifications made to the original wet tower and preserving the condenser operating condition, the accomplished amount of water conservation is satisfactory.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.