Abstract

We presented results of experimental research into dynamics of hazardous factors of the state of environment, as well as of their autocorrelations and pair correlations in a simulation chamber at various lags for early detection of ignition of combustible materials, such as alcohol, paper, timber and textiles. The study was carried out based of Pearson coefficient of lag correlation that possesses the best interpretability of results. It was found that dynamics of factors of the state of environment in space of the studied factors prior to ignition of materials is locally inhomogeneous and distributed with random transitions between local states. At ignition, in the studied environment, there occurs grouping of its distributed local states depending on material of ignition. It was established that the character of grouping can be used as an indicator of early detection of ignition and identification of the type of combustible material. In this case, early ignition causes a slight increase in constant of time of fluctuations of the studied factors of environment. However, this indicator has insufficient differentiability for early detection of ignitions. A more informative indicator is a degree of mutual correlation of fluctuations of environmental factors at zero lag. It was found that for alcohol, paper, timber and textiles, an effective indicator of early detection of their ignition is coefficient of pair correlation of CO and temperature, the module of which is close to 1, and for textiles – to –1

Highlights

  • Prevention of ignition in premises is one of the most important problems of safe development of community

  • In order to solve the first problem of the experiment, we studied dynamics of the state of environment in the chamber on the intervals of absence of ignition and beginning of ignition of materials, such as alcohol, paper, timber and textiles

  • Analysis of the research results reveals that more informative indicator for early detection of ignition is a degree of mutual correlation of fluctuations of environmental factors (Fig. 5–8) at zero lag

Read more

Summary

Introduction

Prevention of ignition in premises is one of the most important problems of safe development of community. In the framework of this trend, the authors developed new technologies of joint processing of information on two or more factors for reliable early detection of ignition in the premises. First of all, it is development of technologies of multi-sensor ignition detection [7]. Because of complexity and diversity of actual ignitions, while substantiating technologies of multi-sensor detection, the properties of major hazardous factors of ignition remain insufficiently studied. In this regard, the study of the properties of major factors of ignition of combustible materials is relevant

Literature review and problem statement
The aim and objectives of the study
Theory behind the experiment
Conclusions
Results
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.