Abstract

The short-circuit reactance is an important parameter to characterize the transformer ability to resist the attack of short-circuit current in the design the operation process. In this paper, the on-line measuring method for short-circuit reactance based on electrical parameters' characteristics was presented, and the feasibility to carry out on-line monitoring for the transformer operation condition was also analyzed. Besides, the principle of two on-line measuring methods based on respectively exciting current compensation and elimination technique was researched, and the calculation equations were deduced. The comparison between the on-line results measured from moving mold experiment and those from off-line short-circuit experiment showed that these two methods were accurate and valid.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.