Abstract

To forecast power transformer fault, this paper proposed a integrated algorithm. Research found that discrete time series of power transformer dissolved gases concentration have 2 main types: the s type and the monotone increasing type. The gray verhulst model was chosen for forecasting the s type series, while the gray model predicted the monotone increasing type data. The two models combined a new integrated forecast model. The fault diagnosis method combines the improved three-ratio method and gray artificial immune algorithm, so it can diagnoses both single and multi power transformer faults, and give the fault location. Experiments show that the power transformer fault forecast algorithm is effective and reliable.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.