Abstract

The real stator bars of an 18kV pumped storage generator were taken as research objects. The multi-factor sequential aging tests of thermal cycling, electrothermal and vibration were carried out. The dielectric loss angle tangent (tanδ), capacitance (C), Δtanδ, ΔC and maximum partial discharge of the samples at different aging periods were measured. The variation of these parameters with aging time was summarized, and the aging mechanism was analysed. The results show that tanδ, Δtanδ, and ΔC increase overall with aging time, while the capacitance decreases slightly with aging time. The maximum partial discharge decreases gradually at beginning of aging, and then increases after aging of 4 periods. All of tanδ, Δtanδ, ΔC and maximum partial discharge increase obviously in the later stages of aging. They can be used as characteristic parameters for multi-factor aging of stator bars insulation of pumped storage generators, to evaluate the aging state of the insulation with epoxy mica.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.