Abstract

The paper presents the research results on electrostatic charging tendency (ECT) of transformer oil in a spinning disk system. The measurements were performed at different aging severity. Changes in static electrification were related to some classical aging indexes (conductivity, dissipation factor, water content, resistivity, etc.). Fast, inexpensive and reliable laboratory testing procedures developed by ASTM (D 6802 and D 6181) were also used to monitor the decay products as trace impurities. The obtained results show that static electrification currents increase with temperature, oil flow velocity, coating disk material properties and oil’s aging byproducts. The polarity, the amplitude and the time constant of the streaming electrification currents are also affected. This contribution is not only intended to provide a fresh review in this domain of research, but also contains a substantial amount of new material with a view of closing some gaps in the present state of knowledge of transformer oil streaming electrification phenomenon.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.