Abstract
The propagation of HVDC converter station generated RF signals through a 345 kV AC switchyard to injection on the AC lines has been examined. A one-line analytical model of the AC buses, yard equipment and converter transformers has been formulated based upon measured RF impedances. The calculations were compared with relative measurements of RF line currents as different filter banks were switched in and out. The results indicate that the model will be a promising means of analysis and mitigation of unwanted RF effects. Phase-to-phase coupling and extension of the approach to a three-line model have been considered but absolute RF measurements would be required prior to any definitive assessment.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.