Abstract
Distributed bus protection is one of the main tasks of smart substation construction to improve the secondary system because it is economical, simple, easy to layout, and easy to realize double. This paper mainly considers that distributed current differential protection is limited by high precision synchronization and high bandwidth and a distributed bus protection based on the directional impedance element comparison principle is proposed. The bus impedance protection constructed by reverse current calculation is proposed, which the impedance protection with positive sequence polarization and the impedance protection with memory polarization are the main components. Further considering the influence of system oscillation, the power frequency variable distance protection is introduced to form a distributed bus protection system, and the setting and time setting principles are given. The principle of the protection system is simple and the action is reliable. The effectiveness of the protection system is verified based on PSCAD simulation software.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.