Abstract

SUMMARYWhen a fault arc occurs in oil‐filled electric power equipment such as transformers in transmission and distribution systems, it generates a flammable gas and a dynamic pressure rise that may trigger an explosion. The purpose of this fundamental study is to investigate the effects of the arc under electrical insulation oil on pressure rises in a closed vessel containing air and oil. In particular, this paper is intended to investigate the relationship between the pressure rises and the generated bubble behavior by the arc. The pressure rises in both air and oil are measured under experimental conditions involving an arc current ranging from 2.3 kA to 8.9 kA, an arc duration of 10 ms or 100 ms. Experimental results show that the behavior of a bubble affects the pressure rises in the air and the oil as low‐frequency pressure oscillation comparatively.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.