Abstract

Attention is focused on the issues of flow resistance and pressure drop of perspective refrigeration fluids during condensation in the two-phase flow in minichannels. The case of the flow through a cylindrical single channel of 2.3 mm inner diameter was carefully analyzed. Pressure drop tests have been performed in diabatic flow conditions. The effect of heat flux, mass flux, vapour quality and saturation temperature on the two-phase pressure drop have been scrutinised. In the course of investigations, the new fluids, namely HFE 7100 and HFE 7000, have been tested. Calibration of the measurement system for the case of single phase flow and comparison of the results with the Blasius friction correlation show the accuracy of ±15%. Additionally, the data were compared with some well established correlations for two-phase flow exhibiting that the correlation due to Fronk and Garimella (2010) and the in-house model are found in best agreement with the experimental data.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.