Abstract

Temperature and leakage current on the ZnO arrester are interrelated with each other. In low conduction region, voltage-current characteristics of ZnO surge arrester are highly dependent on temperature. The leakage current will increase as the temperature increases and experience thermal runaway when the temperature exceeds the acceptable limit. This phenomenon is associated with the increase of resistive leakage current due to degradation. Therefore the temperature and leakage current are good indicator to evaluate the condition of ZnO arrester. This paper proposed the degradation prediction of ZnO surge arrester by analyzed the temperature and leakage current. The 132 kV station type ZnO surge arrester was employed. Temperature profile of ZnO arrester was obtained using thermal camera. The leakage current was measured simultaneous with the temperature measurement to attain the leakage current at the actual temperature. The results shows the leakage current continue increasing by increasing the temperature. Keywords : Resistive leakage current, temperature, degradation, prediction, zinc oxide surge arrester

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.