Abstract

Many research works have proved that it is viable to predict the radio interference (RI) of high-voltage alternating current transmission lines by corona cage test. However, it is uncertain whether the same method can be adopted for RI prediction of high-voltage direct current (HVDC) transmission lines, since the corona performance of HVDC lines is obviously affected by the widely distributed space charge. In this study, the detailed corona current characteristics, such as the current pulse amplitude, rise time, half-wave time, and repetition frequency are systematically studied by the reduced-scale experiment and the relationship between the average corona current and the RI excitation current is confirmed. Furthermore, based on the experimental study, a method for predicting the RI level of HVDC transmission lines by the corona cage test is proposed. The RI level of a ±800 kV bipolar HVDC transmission line is predicted and compared with the measured result, which verifies the validity of the proposed method.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.