Abstract

In this paper, a prediction model for the crystallization fouling was proposed on the basis of the Kern-Seaton model for the heat transfer and fouling process in circulated cooling water. The fouling deposition and removal process were analyzed, respectively, for the fouling process, on which the coupling effects of the scale layer, temperature and ions concentration were considered. The model calculation may predict the fouling resistance variations in fouling process, which were in good agreement with experimental data from references within a range of given conditions especially for the turbulent flow, indicating the model applicability for actual process. Since the model can be used without requirement of a large amount of measured data for fitting, it gives a more convenient way for predicting fouling process of heat exchangers in industry.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.