Abstract

Dissolved Gas Analysis (DGA) for oil samples has been the most widely used diagnosis tool for transformer condition assessment for many years. However, DGA use to oil-filled transformers with a voltage class up to 100 kV. The aim of this paper is to address the issue of DGA interpretation to oil-filled transformers with a voltage class of 10 kV. This paper will present DGA tests results from 57 power transformers and will propose a maintenance decision making procedure using the IEC 60599-2015 Ratio Method, IEEE Std C57.104-2008 include Dornenberg Ratio Method and Rogers Ratio Method, and Russian Std CTO 56947007-29.180.010.094-2011 and Russian Std RD 153-34.0-46.302-00.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.