Abstract
Post-arc current measurements were made on a high-voltage SF/sub 6/ circuit breaker. A pyrotechnic device was used to protect the measurement shunt. The tests, performed at high current values between 40 and 63 kA, gave post-arc current levels of 0.5 to 2 A. Interpretation of the experimental results by the generalized Mayr model led to the determination of a set of parameters characteristic of the apparatus tested, thereby making it possible to find the test results and, in particular, to forecast cases of thermal failure.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.