Abstract

This paper proposes a method for estimating two inductances and capacitance of an LCL filter, connected between a converter and a grid. Only the dc-bus voltage and converter phase currents need to be measured. An excitation signal is fed into the converter voltage reference. The fundamental and selected harmonic components are removed from the stored identification data to prevent biases in the parameter estimates. The parameters of the hold-equivalent discrete-time model are estimated recursively. The inductance and capacitance estimates are calculated from the estimated discrete-time parameters using the corresponding closed-form model. The proposed method can be added to the existing converter control algorithms. It can provide the parameter estimates for the converter control. Further, it can be run occasionally during the normal operation in order to obtain an updated grid inductance estimate. Experimental results show that the proposed method yields very good parameter estimates and that it can also detect the changes in the grid inductance.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.