Abstract

AbstractThis paper reports an experimental study on the physical properties of a sprinkler water spray. The mass flux density, shape of spray pattern, size distribution and velocity of water droplets discharged from two types of 15 mm orifice sprinkler heads were measured. Three operating flow conditions of the sprinkler system, including one specified for the Ordinary Hazard class under the LPC rules for sprinkler design, were set. The sprinkler head was installed above finished floor levels of either 2 m or 2.2 m. The median droplet size was found to be related to the water pressure and the orifice diameter of the sprinkler head as proposed by Dundas. The droplet size distribution function can be fitted by a Rosin–Rammler function.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.