Experimental research results are presented concerning the condensation of the R404A refrigerant in a five-channel multiport, which is fed in parallel and consists of mini-channels with internal diameter d=0.90 and 3.30mm. The research was performed in the presence of periodic instabilities generated in a frequency range from 5 to 0.2Hz. During condensation in the multiport, the impact of instabilities is considerably stronger that in the case of single mini-channels. It was found that the temperature profiles and pressure profiles became deformed in each of the mini-channels of the multiport during the condensation process with the generated instabilities. These deformations decreased the value of heat transfer coefficient h, whose value depends on the diameter d of the multiport mini-channels, vapour quality x and the frequency f of the disturbances generated.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.