Abstract
Aim To compare the performance of various types of airflow system in operating theatre. Methods Besançon Hospital has three types of airflow system in operating theatre: laminar (unidirectional) flow, stabilized flow and turbulent flow. We have compared performances of these airflow systems during operations by evaluating several indicators: number of airborne particles, microbial contamination, kinetics of decontamination, rate of mixing and an index of functionality. Results At rest, performances of stabilized flow are close to these of laminar flow. On the other hand, during operations, the laminar flow is the single airflow system to reach the class B10. Conclusion Our study suggest that laminar flow should be used for prosthetic orthopaedic surgery. However, clinical studies are needed to confirm the superiority of laminar airflow systems in operating theatre.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.