Abstract

Even though a dual evaporator ejector cycle (DEEC) offers several advantages over a standard two-phase ejector cycle, few experimental investigations of the performance of the DEEC are available in the literature. This study presents the performance characteristics of an R410A air-conditioner adopted with a DEEC under various operating conditions and ejector geometries. The COP of the DEEC decreased with an increase in entrainment ratio (ER) due to the decrease in pressure lifting ratio. For the optimum ER, the effectiveness of the DEEC increased with an increase in compressor speed with a larger total mass flow rate. The optimum mixing section diameter was determined to be 5 mm based on the cooling seasonal performance factor (CSPF) and CSPFbin of the DEEC. The maximum allowable limit for the ER was also suggested to be 0.3. In addition, the CSPF of the DEEC was 6.3% higher than that of the baseline cycle at an ER of 0.1.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.