Abstract
Refrigerant and heat exchanger design are significant factors of interest in Heat Pump Water Heater (HPWH) system. This paper presents the experimental study about R1234yf as a low global warming potential (GWP) drop-in substitute of R134a. Then condenser configuration analysis is conducted to explore the effects of condenser circuit number using the baseline R134a. It is experimentally demonstrated that the cooling capacity and COP obtained with R1234yf in a HPWH system is slightly lower than that obtained with R134a. It has been shown that R1234yf can be a desirable alternative for R134a with comparable performance but it is noted that extensive modifications should be considered if the same system performance need to be obtained. By closing the valves at the inlet and outlet of one condenser circuit, a one-circuit condenser system could be achieved. It is shown that a system operating with one-circuit condenser only brings the COP down within 5.5%.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.