Abstract
As described in Part I, the supermarket simulation software “SuperSim” with its integrated refrigeration, building and HVAC system models, can be used to evaluate, compare and optimize alternative supermarket refrigeration systems. In Part II the model was used to evaluate and compare the performance of a CO 2 booster refrigeration system with that of a conventional R404A multiplex system in a supermarket application. Floating head pressure control was implemented for both systems when they were in subcritical cycles. For the CO 2 system, when the system was in transcritical cycle due to higher ambient air temperature, the head pressure was optimized through extensive thermodynamic cycle analysis as a function of ambient air temperature. The performance of the CO 2 booster system in the supermarket was then simulated during a one year period and compared with that of the R404A system. As a result, the system performance will benefit from a lower ambient temperature and a sizeable heat recovery for the CO 2 system.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.