Abstract

A theoretical analysis of the ejector refrigeration system based on the constant area ejector flow model is performed. Optimised results for R-123 are presented. It is determined that the variations in condenser and evaporator temperature have a greater effect on the optimum coefficient of performance (COP) than the variation in generator temperature. At the same operating temperatures of the ejector refrigeration system, the optimum COP and area ratio determined in this study using the constant area flow model are greater than the values given in the literature for the constant pressure flow model. For the same area ratio, the COP for the system with the constant pressure ejector is relatively higher than that with the constant area ejector. In this case, however, the condenser temperature should be lowered. In addition, the refrigeration systems have almost the same COP values at lower evaporator or higher condenser temperatures.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.