Abstract

One key factor for a successfull penetration of wind turbine (WT) products into the market is certification. For the development and certification purpose, a 1 MW test-rig for WT nacelles has been developed at RWTH Aachen University which offers the possibility of WT testing with emulated environmental conditions. In this paper, the performance characteristics of a doubly-fed-generator (DFG) on the developed test-rig is discussed. Firstly, the effect of filter impedance of the grid emulator on the controller performance is analyzed under normal grid conditions. Secondly, the transient characteristic of a DFG WT considering the grid emulator setup is identified. A simulation is performed to verify the analysis. Under normal grid condition, the impedance of the grid emulator does not influence the controller of the DFG WT significantly. For fault-ride-through (FRT) tests with a grid emulator, only the series inductive elements of the grid emulator's filter influence the transient characteristic of the DFG WT. The developed 1-MW test-rig fulfills the technical requirement for FRT test in terms of the grid impedance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.