Abstract

Abstract This paper is the first technical status report of a continuing evaluation of ozone treatment for cooling tower water. Data will be presented that illustrate the results of ozone treatment in a 3,400-ton air-conditioning cooling system at the Oak Ridge Y-12 Plant, Oak Ridge, Tennessee, which is operated by Martin Marietta Energy Systems, Inc., for the U.S. Department of Energy. Heat transfer data and equipment inspections confirm that a threshold surface temperature exists, below which heat exchange surfaces remain free of mineral scale. Heat exchange surfaces that exceed the temperature threshold experience calcium carbonate scaling. The temperature threshold effect may explain why ozone treatment has been reported as a successful treatment for air conditioning cooling towers, but has not been successful in higher temperature process cooling systems. Plans for future ozone investigations will be discussed.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.