Abstract

The corona discharge of EHV transmission lines in high altitude area is very serious. Based on the Jiantang-Yulong 500kV power transmission project, we using Ansys software to calculate the surface electric field of 500 kV double circuit AC transmission line insulator and fittings. We get the voltage distribution of upper and middle and lower phase insulator string and the surface electric field distribution of fitting. According to the method of standard recommend, we get the corona electric field of fittings in high altitude (4km) are and compared with the result of the calculation. Then, we gives the optimization scheme of equalizing ring is rotated by 90 DEG and diameter increased to 55mm. The results show that the optimization scheme can effectively reduce the maximum electric field strength of the pressure ring and below the corona electric field value of fittings in high altitude.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.