Abstract

For heat exchanger networks with stream splits, we present a simple way of controlling the split ratio. We introduce the “Jäschke Temperature”, which for a branch with one exchanger is defined as TJ=(T−T0)2/(Th−T0), where T0 and T are the inlet and outlet temperatures of the split stream (usually cold), and Th is the inlet temperature of the other stream (usually hot). Assuming the heat transfer driving force is given by the arithmetic mean temperature difference, the Jäschke Temperatures of all branches must be equal to achieve maximum heat transfer. The optimal controlled variable is the difference between the Jäschke Temperatures of each branch, which should be controlled to zero. Heat capacity or heat transfer parameters are not needed, and no optimization is required to find the optimal setpoints for the controlled variables. Most importantly, our approach gives near-optimal operation for systems with logarithmic mean temperature difference as driving force.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.