Abstract

Recently, there has been significant interest in developing the modular multilevel converter (MMC) based DC grids in the power industry. However, the immature DC circuit breaker (DCCB) technology hampers the development of DC grids in overhead lines transmission field. The full controlled power electronic devices based hybrid DCCB has been proposed and researched substantially. But the hybrid type DCCB suffers from the drawback of high cost and low reliability, leading to high capital cost for DC grids that require numerous DCCBs. In this paper, a mechanical type DCCB, consisting of a mechanical switch, a circuit and an oscillation circuit, is proposed. Then, a four-terminal bipolar MMC-HVDC system implementing the mechanical DCCBs is studied. Extensive simulations have been conducted to analyse the transient performance under different fault conditions. The simulation results verify the technical feasibility of this mechanical DCCB in DC grid.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.