Abstract

Real-time estimation of the equivalent grid impedance and the equivalent grid voltage seen from a power converter connected to the public electric distribution network by means of Extended Kalman-Filter is addressed. The theoretical background of the Extended Kalman-Filter used for equivalent grid impedance estimation is introduced. Practical aspects like the use of the filter in an environment with highly distorted voltage waveforms, the tuning of the noise covariance matrices and the implementation on a laboratory system are discussed. The theoretical analysis is verified on a 22 kW test-bench where a grid impedance emulator is used to simulate grid impedance steps in the laboratory environment. The proposed Extended Kalman-Filter is designed to utilize the noise that is already present at the connection point of the power converter to overcome the need of active disturbance injection to estimate the equivalent grid impedance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.