Abstract

The problem of picking protective current transformers (CT) in order to ensure proper functioning of differential protection in transient regimes is examined. It is proposed that the accuracy limit factor K lim referenced to the nominal current of a power transformer be used as the main parameter in choosing CT. Amethod is presented for calculating K lim as a function of the time to saturation t s, the decay time constant of the aperiodic component of short-circuit (SC) current, and the residual induction and current of external SC. It is shown that increasing K lim results in smaller CT errors in the time interval of the saturated state of a magnetic circuit. It is pointed out that the effect of screening must be taken into account in finding K lim for CT which do not have a proper primary winding and are arranged in phase with screened conductors.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.